Compressor windings and the breaker

When the breaker trips on a cooling call, three readings tell you whether it's the capacitor, the compressor or the power.

The short version

On the job

  1. Fan only from the thermostat. Runs clean: the fault is in the compressor circuit.
  2. Power off, discharge the capacitor. Test HERM and FAN sections against the label.
  3. Ohm C-R, C-S, R-S. The two small readings add up to the large one. Each terminal to the case must read O.L.
  4. Clamp the start: high for under a second is normal. Pegged for seconds is locked or shorted.
  5. Meter voltage at the unit during the start. Under 108 V: fix the supply before you condemn the compressor.

Numbers

Shop tip

Rooftop compressors aren't rebuilt in the field. A grounded winding means a new unit, and the note should say what you measured.