Shore power: 30A vs 50A

30 amp is one 120V leg. 50 amp is two 120V legs. Half the coach dead on a 50 amp rig? One leg is probably missing.

The short version

On the job

  1. Meter the pedestal before you plug in: hot to neutral 120, hot to ground 120, neutral to ground about 0.
  2. 50 A: both hots 120 to neutral and 240 between them. 0 between them means both terminals are on the same leg.
  3. Look at the plug and inlet blades for heat. A darkened neutral blade on a 50 A plug is an open neutral waiting to happen.
  4. Under load, meter at the panel: under about 104 V is a problem for the ACs and the converter.

Numbers

Shop tip

A burnt or discolored plug blade means a loose, high-resistance connection. Replace the end, don't just clean it.