Thermostats and AC control boards

A lot of AC calls are the thermostat or control system, not the AC itself.

The short version

On the job

  1. Blank thermostat: 12V at its harness. Most run from a small fuse at the panel or 12V from the AC's control box.
  2. Jumper the call at the thermostat (furnace) or check the data cable (AC) to split thermostat from appliance.
  3. CCC2 codes: E1 comm cable, E2/E3 indoor sensor, E4 outdoor, E5 freeze, E7 lost 120V, E8/E9 zone DIP switches.
  4. Two zones: unique DIP settings on each rooftop board, then power cycle and re-pair.

Try it on a service call

Put the lesson to work on a hands-on troubleshooting case.